Data Center Cooling & HVAC Quiz
Ten questions on how heat leaves the data hall, from airflow management to chilled water math and liquid cooling. Each answer comes with a short explanation.
Quiz questions
-
Show answer
Answer: the CRAC has a compressor; the CRAH uses chilled water. A computer room air conditioner runs its own refrigeration cycle and rejects heat through a condenser. A computer room air handler is fans plus a chilled-water coil, so it depends on the chiller plant. Read the cooling guide.
-
Show answer
Answer: 18 to 27 °C (64.4 to 80.6 °F). The ASHRAE TC 9.9 thermal guidelines measure this at the server inlet, not at the cooling unit return. Allowable ranges are wider, and running cold aisles colder than needed wastes energy. Cooling Systems Design & Optimization covers the guidelines.
-
Show answer
Answer: about 10 tons. Nearly all power used by IT equipment becomes heat. One kW equals 3,412 BTU/hr and one ton equals 12,000 BTU/hr, so 35 kW is about 119,400 BTU/hr, or roughly 10 tons. Try the cooling load calculator.
-
Show answer
Answer: the cold supply air temperature. Hot aisle containment captures exhaust behind the racks and returns it to the cooling units through a ceiling plenum or chimney, so the rest of the room becomes one large cold aisle. Cold aisle containment does the opposite: only the contained aisle is cool and the room runs warm. Cooling Systems Design & Optimization compares both approaches.
-
Show answer
Answer: supply air that never passes through IT equipment. Bypass air is cooling capacity you paid for that never touches a server. Common causes are unsealed cable cutouts, perforated tiles in hot aisles, and supplying more air than the servers draw, while hot air curling into inlets is recirculation, the opposite problem. Energy Efficiency & PUE Optimization covers airflow fixes.
-
Show answer
Answer: to stop exhaust from recirculating to server intakes. Open rack units let hot air flow from the back of the rack to the front, where servers pull it in, and let cold air short-circuit to the hot side. Blanking panels are one of the cheapest airflow fixes in a data hall. HVAC Systems Troubleshooting Essentials covers hot spot diagnosis.
-
Show answer
Answer: it uses outdoor conditions to cut compressor cooling. An airside economizer uses outdoor air directly or through a heat exchanger. A waterside economizer uses cooling towers or dry coolers to cool the chilled water loop through a heat exchanger, so the chillers can slow down or shut off. Energy Efficiency & PUE Optimization covers free cooling.
-
Show answer
Answer: it doubles. With a fixed load, flow and delta T are inversely related, so half the delta T needs twice the water. That is why "low delta T syndrome" drives up pump energy and can force extra chillers online; dirty coils, open bypass valves, and poor setpoints are common causes. Mechanical Systems & Equipment Maintenance covers the chilled water plant.
-
Show answer
Answer: it isolates and controls the coolant loop to the cold plates. The CDU uses a heat exchanger and pumps to keep the clean, tightly controlled technology cooling loop separate from the facility water system. It also filters the loop and alarms on leaks or pressure changes. Read how AI data centers use liquid cooling.
-
Show answer
Answer: technicians whose work could release refrigerant. Section 608 certification is earned through EPA-approved certifying programs in Type I, II, III, or Universal categories, based on the equipment serviced. Data Center Cooling System and Refrigerant Safety Training covers refrigerant hazards and handling awareness; it does not replace Section 608 certification.
Your score
Cooling pro
You think in airflow, delta T, and tons. Put it on paper: the Cooling & Facilities Efficiency Bundle documents that knowledge with a certificate of completion for every course.
Solid foundation
You have the core ideas. Gaps in airflow management or chilled water math are exactly what Cooling Systems Design & Optimization and HVAC Systems Troubleshooting Essentials close.
Room to grow
Everyone starts somewhere. Read the cooling guide, then start with Cooling Systems Design & Optimization.
Your answers
Courses That Cover These Topics
Every question above maps to a self-paced course. Each awards a certificate of completion.
Cooling Systems Design & Optimization
Cut cooling costs and improve reliability with modern thermal management strategy.
HVAC Systems Troubleshooting Essentials
Hands-on troubleshooting skills for CRAC/CRAH systems and common cooling failures.
Mechanical Systems & Equipment Maintenance
Hands-on mechanical maintenance — piping, chillers, and vibration diagnostics.
Data Center Cooling System and Refrigerant Safety Training
Refrigerant handling and cooling system safety practices specific to data center CRAC/CRAH environments.
Energy Efficiency & PUE Optimization
Cut operating costs with a measurable PUE optimization roadmap.
Save 42% with the bundle
Cooling & Facilities Efficiency Bundle
Keep Going
Brush up with the guide, size a load with the calculator, or try another quiz.